 SENSOR MODULE  CHB-500S (T)  | 
| 
 The SENSOR Module CHB-500S is a closed loop Hall current sensor to measure 500A DC, AC or pulsed   | 
| 
 currents with a galvanic isolation between the primary and secondary circuits.  | 
| 
    | 
| 
 Closed-loop Hall Current Sensor:  | 
| 
 Type  | 
 Nominal current  | 
 Output current  | 
 Accuracy  | 
 Supply voltage  | 
 Aperture  | 
| 
 IN(A)  | 
 IM(mA)  | 
 X(%)  | 
 Vc(V)  | 
 mm  | 
| 
 CHB-500S  | 
 500  | 
 100  | 
 ±0.5%  | 
 ±15~24  | 
 ¢25  | 
| 
 CHB-500T  | 
 500  | 
 100  | 
 ±0.5%  | 
 ±15~24  | 
 Bus bar  | 
| 
    | 
| 
 Specifications:    | 
| 
 Principle  | 
 Closed loop Hall effect principle  | 
| 
 Input current  | 
 500A(DC、AC、Pulsed current)  | 
| 
 Output current  | 
 100mA  | 
| 
 Turns ratio  | 
 1:5000  | 
| 
 Frequency  | 
 DC~100KHz  | 
| 
 Accuracy  | 
 ±0.5%  | 
| 
 Response time  | 
 <1μS  | 
| 
 Linearity  | 
 <0.1%  | 
| 
 Supply voltage  | 
 ±15~24V(±5%)  | 
| 
 Consumption  | 
 35mA+IM(Output current)  | 
| 
 Isolation voltage  | 
 Between primary and secondary circuit: 6KV RMS/50Hz/1min.  | 
| 
 Operating temp.  | 
 -25…+85℃  | 
| 
 Mounting on  | 
 Fastening on panel  | 
| 
 Applications  | 
 Power supplies, welding machines, converters, industry auto-control, motor drives,  | 
| 
 For industry  | 
 electronic power system, railways, rectifiers systems etc.  | 
| 
 >>Back  |