Name/Model: |
DC current transducer CHZ-*AD |
Rated input Parameter: |
DC 0.02A~30A current |
|
SENSOR MODULE CHZ-* AD |
The SENSOR Module CHZ-*AD is a signal conditioning DC current transducer to measure 0.02A…30A DC current |
with a galvanic isolation between the primary and secondary circuits. |
|
Signal conditioning DC current transducer: |
Type |
Nominal current |
Signal output |
Accuracy |
Supply voltage |
Connection |
IN(A) |
VM / IM |
X(%) |
Vc(V) |
Input |
CHZ-002AD/# |
0.02 |
A0, A1, V0 |
±0.5% |
+24 |
Terminals |
CHZ-005AD/# |
0.05 |
See table 1 |
|
|
|
CHZ-01AD/# |
0.1 |
|
|
|
|
CHZ-05AD/# |
0.5 |
|
|
|
|
CHZ-1AD/# |
1 |
A0, A1, V0 |
±0.5% |
+24 |
Terminals |
CHZ-5AD/# |
5 |
|
|
|
|
CHZ-10AD/# |
10 |
|
|
|
|
CHZ-15AD/# |
15 |
A0, A1, V0 |
±0.5% |
+24 |
Terminals |
CHZ-20AD/# |
20 |
|
|
|
|
CHZ-30AD/# |
30 |
|
|
|
|
Note: Type named, such as CHZ-002AP/V0 Nominal input current: 0…0.02A, Signal output: 0…5V |
|
Table 1: # |
A0 |
A1 |
V0 |
|
|
Signal output |
0…20mA |
4…20mA |
0…5V |
DC |
|
|
Specifications: |
Input current |
0.02…30A (DC current) |
Signal Output |
A0, A1, V0, (See table 1) |
Frequency |
DC |
Accuracy |
±0.5% |
Response time |
<0.35S |
Linearity |
<0.5% |
Supply voltage |
+24V(±5%) |
Consumption |
90mA |
Isolation voltage |
Between primary and secondary circuit: 2.5KV RMS/50Hz/1min. |
Operating temp. |
-25…+85℃ |
Mounting on |
Fastening on panel |
Applications |
Power supplies, industry auto-control, motor drives, electronic power system, railways etc. |
>>Back |
|
|
|
|