SENSOR MODULE CHG-200E~1000E (B) |
|
The SENSOR Module CHG-200E~1000E is a current transformer to measure 5A…100A AC current with |
|
a galvanic isolation between the primary and secondary circuits. |
|
|
|
Current Transformer: 400Hz…20KHz |
|
Type |
Nominal current |
Output current |
Accuracy |
Turns ratio |
Aperture |
|
IN(A) |
IM(mA) |
X(%) |
KN |
mm |
|
CHG-200E |
20~100 |
IN / KN |
±0.5% |
1:200 |
¢12 |
|
CHG-500E |
|
|
|
1:500 |
|
|
CHG-1000E |
|
|
|
1:1000 |
|
|
|
|
Current Transformer: 50Hz (400Hz) |
|
Type |
Nominal current |
Output current |
Accuracy |
Turns ratio |
Aperture |
|
IN(A) |
IM(mA) |
X(%) |
KN |
mm |
|
CHG-500EB |
5~100 |
IN / KN |
±0.2% |
1:500 |
¢12 |
|
CHG-1000EB |
|
|
|
1:1000 |
|
|
|
|
Specifications: |
|
Principle |
Transformer principle |
|
Input current |
5…100A AC current |
|
Output current |
IN / KN |
|
Turns ratio |
1:200~1000 |
|
Frequency |
50Hz (400Hz), 400Hz…20KHz |
|
Accuracy |
±0.2~±0.5% |
|
Response time |
<10uS |
|
Linearity |
<0.1% |
|
Supply voltage |
No need |
|
Consumption |
No need |
|
Isolation voltage |
Between primary and secondary circuit: 2KV RMS/50Hz/1min. |
|
Operating temp. |
-40…+85℃ |
|
Mounting on |
Fastening on panel |
|
Applications |
Power supplies, welding machines, converters, industry auto-control, motor drives, |
|
For industry |
electronic power system, railways, rectifiers systems etc. |
|
>>Back |